Electrical · Cost & Calculation

FRLS Wire Quantity Calculation for House Wiring: Metres and Coils by Circuit

How many metres and 90 m coils of FRLS wire each circuit needs, by size and colour, with a worked 2BHK example.

On this page
  1. What Is FRLS Wire and Why Use It for House Wiring?
  2. How Do You Calculate FRLS Wire Quantity for House Wiring?
  3. What Is the Formula for House Wiring Wire Length?
  4. Worked Example: FRLS Wire Quantity for a 2BHK House
  5. What Factors Change House Wiring Wire Quantity?
  6. How Do You Keep FRLS House Wiring Safe and Compliant?
0%
Summary — what you need to know
  • Each circuit needs three wires: phase, neutral and earth.
  • Our 2BHK example needs 3 coils of 1.5 sq mm and 6 coils of 4 sq mm.
  • Add a 10% allowance to the run, divide by 90 m per coil, round up.
  • CPWD sets 1.5 sq mm for lights and 4 sq mm for power circuits.

FRLS wire quantity calculation for house wiring starts from your circuit list. Measure each circuit's conduit run, add 10% and divide by the 90 m coil, for each size and colour.

90 m
Standard house wire coil length
10 points
Max per lighting circuit, or 800 W (CPWD)
3 wires
Phase, neutral and earth per circuit

What Is FRLS Wire and Why Use It for House Wiring?

FRLS wire is a flame retardant, low smoke PVC insulated copper wire. BIS calls this category FR-LSH under IS 694:2010, the Indian standard for PVC insulated cables up to 1,100 V.

Unlike plain FR wire, FR-LSH wire also passes smoke density and acid gas tests. KEI's Conflame FR-LSH data sheet lists 60% maximum smoke density and 20% maximum acid gas. FR and FRLS share the same sizes and 90 m coils, so FRLS changes the grade, not the quantity.

How Do You Calculate FRLS Wire Quantity for House Wiring?

You calculate it circuit by circuit, then convert metres into coils.

  1. List lighting circuits: 10 points or 800 W each, whichever is less.
  2. Group sockets: two 16 A, three 6 A, or one 16 A plus two 6 A per circuit (CPWD clause 3.10).
  3. Measure each run: trace the conduit from the distribution board (DB) to every point along walls and ceilings, never in straight lines.
  4. Assign a size: 1.5 sq mm for lighting, 4 sq mm for power.
  5. Convert: add 10% for switch loops, divide by 90 m per colour, round up.

What Is the Formula for House Wiring Wire Length?

The formula totals the runs of one wire size, adds 10% and divides by the coil length.

The formula
Metres per colour = ΣR × 1.10 · Coils = ⌈ ΣR × 1.10 ÷ 90 ⌉ × 3 colours
ΣR = total conduit run (m) for one wire size; 1.10 = 10% planning allowance; ⌈ ⌉ = round up. Earth matches phase size up to 16 sq mm (IEC 60364-5-54).
Rule of thumb: the MCB protects the wire

A miniature circuit breaker (MCB) must never be rated above the wire it protects. APAR lists 14 A for 1.5 sq mm and 26 A for 4 sq mm in conduit.

Worked Example: FRLS Wire Quantity for a 2BHK House

This example is a single-phase 2BHK of about 1,000 sq ft. Run lengths are illustrative; measure your own plan.

2BHK wiring plan with lighting and power circuit runs from the distribution board, and the coil formula: 72 m of 1.5 sq mm wire needs 3 coils and 114 m of 4 sq mm wire needs 6 coils across three colours

Circuit list and wire per colour

Run × 1.10
CircuitSize (sq mm)Run (m)Per colour (m)
C1 Lights, hall and kitchen1.52628.6
C2 Lights, bedroom 11.52224.2
C3 Lights, bedroom 21.52426.4
C4 Kitchen sockets41415.4
C5 AC, bedroom 141819.8
C6 AC, bedroom 242224.2
C7 Geysers42022.0
C8 Hall sockets41617.6
C9 Bedroom sockets42426.4
Grouping follows CPWD clause 3.10. Count the meter-to-DB submain separately.
Worked exampleMetres and coils by size
1.5 sq mm run: 26 + 22 + 2472 m
Per colour: 72 × 1.1079.2 m
Coils per colour: 79.2 ÷ 90 = 0.88, round up1 coil
4 sq mm run: 14 + 18 + 22 + 20 + 16 + 24114 m
Per colour: 114 × 1.10125.4 m
Coils per colour: 125.4 ÷ 90 = 1.39, round up2 coils
Total wire: 79.2 × 3 and 125.4 × 3237.6 m and 376.2 m
ResultBuy 3 coils of 1.5 sq mm and 6 coils of 4 sq mm (one red, one black, one green set per size)

The 4 sq mm coils leave about 54.6 m spare per colour for a future circuit.

Voltage drop on the 22 m AC run at 14 A, using APAR's 11 mV/A/m: 11 × 14 × 22 ÷ 1,000 = 3.39 V, or 1.47% of 230 V.

What Factors Change House Wiring Wire Quantity?

The number of circuits, the DB position and room height change wire quantity most. Floor area alone is a poor guide.

  • DB placed centrally to shorten every run.
  • Ceiling height counted in every vertical drop.
  • Future AC or EV charging circuits wired now.

See our house electrical wiring planning guide for loads and the conduit wiring explainer for runs.

How Do You Keep FRLS House Wiring Safe and Compliant?

Safe FRLS house wiring uses ISI-marked copper wire, matched MCBs and CPWD colours: red phase, black neutral, yellow-green earth. See house wiring cable selection, and have a licensed electrician check your plan.

60-minute delivery

Got your coil count?

House wires and wiring accessories delivered across Bengaluru.

House WiresMCBs & Distribution BoardsConduits & FittingsSwitches & Sockets
Shop nowBrowse house wiresBengaluru · open 8 am–8 pm, all days

Frequently Asked Questions

How to calculate wire for house wiring?

Measure each circuit's conduit run from the DB and add the runs per wire size. Multiply by 1.10, divide by 90 m and round up for coils per colour.

How much wire for a 1000 sq ft house?

There is no fixed figure per sq ft. Our 1,000 sq ft 2BHK example needs about 238 m of 1.5 sq mm and 376 m of 4 sq mm wire: 3 and 6 coils.

Which wire is best for home, FR or FRLS?

FRLS (FR-LSH) wire is better for homes. It adds smoke density and acid gas tests to FR wire's flame tests under IS 694:2010.